Ethernet Remote IO Module(8DIN+8DO,High speed pulse counter,pulse output)

<
>

Ethernet Remote IO Module(8DIN+8DO,High speed pulse counter,pulse output)

Model no:M140T

M140T Ethernet Remote I/O Module provides 8 optical-isolated digital inputs, supports Max. 700KHz high speed pulse counter, 8 digital outputs, supports 10Hz~300Khz high speed pulse output or relay outputs.It is design for working in the harsh industrial application environment, widely used in a variety of industrial automation, security monitoring system, automatically measurement and control system.

Consult QQ

The M140T Ethernet Remote I/O Module is an industrial class, isolated designed, high reliability, high stability and high precision data acquisition module, embedded 32-Bit High Performance Microprocessor MCU, Integrated 1 Industrial 10/100M adaptive Ethernet module inside. It provides multi I/O, supports standard Modbus TCP, can be intergraded into SCADA, OPC server, and other automation systems. It is design for working in the harsh industrial application environment, widely used in a variety of industrial automation, security monitoring system, automatically measurement and control system.
The M140T Ethernet Remote I/O module provides a RS485 interface, through the RS485 bus, it can cascade Modbus RTU I/O devices or Modbus RTU meters, e.g.: a variety of digital input or digital outputs, analog inputs or outputs, thermal resistance IO module combination, save costs. At the same time, the Ethernet Remote I/O module has register mapping function, the cascade Modbus RTU I/O data are automatically collected to the mapping memory area, the Modbus TCP Client query without waiting then can get a quick response to meet the industrial timely requirements.

The M140T Ethernet Remote I/O module provides 8 optical-isolated digital inputs, supports max. 700KHz high speed pulse counter, 8 digital outputs, supports 10Hz~300Khz high speed pulse output or relay outputs. All of the I/O with high sampling frequency and special filtering strategy to ensure it’s reliable.

Ethernet Remote IO Module

TagsModbus TCP Remote IO ModuleEthernet remote modulepulse counter data acquisition modulepulse output module
1. Embedded 32-Bit High Performance Microprocessor MCU, inbuilt watchdog;
2. Power supply 12~36VDC with over voltage and phase-reversal protection;
3. Management and configuration via LAN connection configuration software for easy operation and maintenance;
4. Integrated 10/100M adaptive Ethernet module, supports Modbus TCP protocol;
5. 8 optical isolated digital input(default is wet contact,if you want dry contact please contact us), supports max. 700Khz high speed pulse counter;
6. 8 digital output (default is sink output), supports 10Hz~300KHz high speed pulse output;
7. High sampling frequency and special filtering strategy to ensure reliability;
8. 1 RS485 Serial port, supports Modbus RTU Master or slave, can extend I/O modules;
9. Supports register mapping function and extend I/O inquiry strategy;
10.Provides 1 channel 12~36VDC power source output for external device, saving wiring cost;
11.LED instructions work status, with reset button to reset, easy on-site installation and commissioning;
12.Using metal shell, protection class IP30. Metal shell and system security isolation, especially suitable for industrial  applications in the field;
13.Small size, L105 * W88 * H30mm, compatible wall installation and DIN35mm industrial rail installation.

M140T Specifications


Ethernet Remote I/O Module Specifications

• Digital Input

Sensor Type

Wet Contact (NPN or PNP), Dry Contact

I/O Mode

DI or Event Counter

Dry Contact

• On: short to GND=1
• Off: open=0

Wet Contact (DI to COM)

• On: 10 to 30 VDC =1
• Off: 0 to 3 VDC=0

Counter Frequency

Max. 700kHz(Only the 1st Channel can be used as high speed pulse counter)

Digital sampling frequency

500Hz

Digital filtering strategy

Continues 3 times

Isolation

Optical Isolated,3k VDC or 2k Vrms

• Digital Output

Type

Sink 

I/O Mode

DO or Pulse Output

Pulse Output Frequency

10Hz~300KHz(Only the 1st Channel can be used as high speed pulse outputs)

Over-Voltage Protection

50 VDC

Over-Temperature Shutdown

175°C (typical), 150°C (min.)

Load Current

Max. 500 mA per channel

Digital sampling frequency

500Hz

• Working Power Requirements

Input Voltage

12~36VDC, Peak Voltage:+40VDC, Power consumption: Less than 3W;

Input Current

139 mA @ 24 VDC

• Power Output

Output Voltage

12~36VDC

Output Current

139 mA @ 24 VDC

• LAN

Ethernet

10/100 Mbps, RJ45 ports

Protection

15KV ESD Protection

Protocols

Modbus TCP, TCP/IP,MQTT,TCP Server, TCP Client 

Max. TCP Connection

5

• Serial Port

RS485

MODBUS RTU over TCP Protocol, Modbus TCP Protocol

Protection

15KV ESD Protection

Modbus Slave address

1~255

Baud Rate

1200,2400,4800,9600,19200,38400,57600,115200,128000Bps;

Mapping registers

Bit Type: 300 Registers, 16-Bit Type: 300 Registers.

• Physical Characteristics

Wiring

I/O cable max. 14 AWG

Dimensions

105 x 88 x 30 mm

Weight

Under 205 g

Mounting

DIN rail or wall

• Environmental Limits

Operating Temperature

Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Ambient Relative Humidity

5 to 95% (non-condensing)

Altitude

Up to 3000 m

Ethernet Remote IO Module User Manual :http://rtu-m2m.com/Download/Manual/EN/New_MxxxT_UserManual.zip



Ethernet Remote IO Module Confiurator:http://rtu-m2m.com/Download/Software/EN/New_MxxxT_ConfigurationTool.zip

Win7 8 10 driver:http://rtu-m2m.com/Download/Software/CP210x_Windows7_8_10_Drivers.zip

EMI Standard :

EN55032:2015;

EN 61000-3-2:2014;

EN 61000-3-3:2013;

EMS Standard:

EN 55024:2010+A1:2015;

EN 1000-4-2:2009;

EN61000-4-3:2006+A1:2008+A2:2010;

EN61000-4-4:2012;

EN 61000-4-5:2014;

EN 61000-4-6:2014;

EN 61000-4-8:2010;

EN 61000-4-11:2004;

CE-LVD Standards:

IEC 60950-1:2005+A1:2009+A2:2013;

EN 60950-1:2006+A2:2013;

EN 62311:2008;

EMC:

ETSI EN 301 489-1 V2.2.0(2017-03);

ETSI EN 301 489-17 V3.2.0(2017-03);

ETSI EN 300 328 V2.1.1 (2016-11)。

Modbus TCP Remote IO Module X1
User Manual X1

Typically applications:

 

1.      BTS Monitoring;

2.      Security Alarm System applications;          

3.      Supervision and monitoring alarm systems;

4.      Automatic monitoring system;             

5.      Vending Machines security protection;

6.      Pumping Stations, Tanks, Oil or Water levels;

7.      Buildings and Real Estate;

8.      Weather Stations; 

9.      River Monitoring and Flood Control;

10.   Oil and gas pipelines;  

11.   Corrosion protection

12.   Temperatures, water leakage applications;

13.   Wellheads, boat, vehicle;

14.   Energy saving, street lights control system;

15.   Valve controls;

16.   Transformer stations;   

17.   Unmanned machine rooms;

18.   Control room application;

19.   Automation System, M2M;

20.   Access Control System;

21.  PLC Gateway, PLC Remote Monitoring.