Ethernet Remote Digital Input Module(4DIN)

<
>

Ethernet Remote Digital Input Module(4DIN)

Model no:M210T

The M210T Ethernet Remote I/O module provides 4 optical-isolated digital inputs, supports max. 700KHz high speed pulse counter. All of the I/O with high sampling frequency and special filtering strategy to ensure it’s reliable.Integrated 1 Industrial 10/100M adaptive Ethernet module inside. It provides multi I/O, supports standard Modbus TCP, can be intergraded into SCADA, OPC server, and other automation systems. It is design for working in the harsh industrial application environment, widely used in a variety of industrial automation, security monitoring system, automatically measurement and control system.

Consult QQ

The M210T Ethernet Remote I/O Module is an industrial class, isolated designed, high reliability, high stability and high precision data acquisition module, embedded 32-Bit High Performance Microprocessor MCU, Integrated 1 Industrial 10/100M adaptive Ethernet module inside. It provides multi I/O, supports standard Modbus TCP, can be intergraded into SCADA, OPC server, and other automation systems. It is design for working in the harsh industrial application environment, widely used in a variety of industrial automation, security monitoring system, automatically measurement and control system.


The M210T Ethernet Remote I/O module provides a RS485 interface, through the RS485 bus, it can cascade Modbus RTU I/O devices or Modbus RTU meters, e.g.: a variety of digital input or digital outputs, analog inputs or outputs, thermal resistance IO module combination, save costs. At the same time, the Ethernet Remote I/O module has register mapping function, the cascade Modbus RTU I/O data are automatically collected to the mapping memory area, the Modbus TCP Client query without waiting then can get a quick response to meet the industrial timely requirements.

The M210T Ethernet Remote I/O module provides 4 optical-isolated digital inputs, supports max. 700KHz high speed pulse counter. All of the I/O with high sampling frequency and special filtering strategy to ensure it’s reliable.

TagsEthernet Remote Digital Input ModuleRemote Digital Input Module
1. Embedded 32-Bit High Performance Microprocessor MCU, inbuilt watchdog;
2. Wide range power supply 12 ~ 36VDC with over voltage and phase-reversal protection;
3. Management and configuration via LAN connection configuration software for easy operation and maintenance;
4. Support Web realtime monitoring and Web debugging;  
5. Integrated 10/100M adaptive Ethernet module, supports Modbus TCP protocol;
6. 4 optical isolated digital input, supports max. 700khz high speed pulse counter;
7. High sampling frequency and special filtering strategy to ensure reliability;
8. 1 RS485 Serial port, supports Modbus RTU/ASCII Master, can extend I/O modules;
9. Supports register mapping function and extend I/O inquiry strategy;
10.Provides 1 channel 12~36VDC power source output for external device, saving wiring cost;
11.LED instructions work status, with reset button to reset, easy on-site installation and commissioning;
12.Using metal shell, protection class IP30. Metal shell and system security isolation, especially suitable for industrial applications in the field;
13.Small size, L105 * W88 * H30mm, compatible wall installation and DIN35mm industrial rail installation.

Ethernet Remote I/O Module Specifications

• Digital Input

Sensor Type

Wet Contact (NPN or PNP), Dry Contact

I/O Mode

DI or Event Counter

Dry Contact

• On: short to GND=1
• Off: open=0

Wet Contact (DI to COM)

• On: 10 to 30 VDC=1 
• Off: 0 to 3 VDC=0

Counter Frequency

Max. 700Khz (Only the 1st Channel can be used as high speed pulse counter)

Digital sampling frequency

500Hz

Digital filtering strategy

Continues 3 times

Isolation

Optical Isolated,3k VDC or 2k Vrms

• Working Power Requirements

Input Voltage

12 to 36 VDC, Peak Voltage:+40VDC, Power consumption: Less than 3W;

Input Current

139 mA @ 24 VDC

• Power Output

Output Voltage

12 to 36 VDC

Output Current

139 mA @ 24 VDC

• LAN

Ethernet

10/100 Mbps, RJ45 ports

Protection

15KV ESD Protection

Protocols

Modbus TCP, TCP/IP

Max. TCP Connection

5

• Serial Port

RS485

MODBUS- RTU Protocol, Modbus-ASCII Protocol

Protection

15KV ESD Protection

Modbus Slave address

1~255

Baud Rate

1200,2400,4800,9600,19200,38400,57600,115200,128000Bps;

Mapping registers

Bit Type: 300 Registers, 16-Bit Type: 300 Registers.

• Physical Characteristics

Wiring

I/O cable max. 14 AWG

Dimensions

105 x 88 x 30 mm

Weight

Under 205 g

Mounting

DIN rail or wall

• Environmental Limits

Operating Temperature

Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Ambient Relative Humidity

5 to 95% (non-condensing)

Altitude

Up to 3000 m

Ethernet Remote IO Module User Manual 



Ethernet Remote IO Module Photos 

EMI Standard :

EN55032:2015;

EN 61000-3-2:2014;

EN 61000-3-3:2013;

EMS Standard:

EN 55024:2010+A1:2015;

EN 1000-4-2:2009;

EN61000-4-3:2006+A1:2008+A2:2010;

EN61000-4-4:2012;

EN 61000-4-5:2014;

EN 61000-4-6:2014;

EN 61000-4-8:2010;

EN 61000-4-11:2004;

CE-LVD Standards:

IEC 60950-1:2005+A1:2009+A2:2013;

EN 60950-1:2006+A2:2013;

EN 62311:2008;

EMC:

ETSI EN 301 489-1 V2.2.0(2017-03);

ETSI EN 301 489-17 V3.2.0(2017-03);

ETSI EN 300 328 V2.1.1 (2016-11)。

Modbus TCP Remote IO Module X1
User Manual X1

Typically applications:

 

1.      BTS Monitoring;

2.      Security Alarm System applications;          

3.      Supervision and monitoring alarm systems;

4.      Automatic monitoring system;             

5.      Vending Machines security protection;

6.      Pumping Stations, Tanks, Oil or Water levels;

7.      Buildings and Real Estate;

8.      Weather Stations; 

9.      River Monitoring and Flood Control;

10.   Oil and gas pipelines;  

11.   Corrosion protection

12.   Temperatures, water leakage applications;

13.   Wellheads, boat, vehicle;

14.   Energy saving, street lights control system;

15.   Valve controls;

16.   Transformer stations;   

17.   Unmanned machine rooms;

18.   Control room application;

19.   Automation System, M2M;

20.   Access Control System;