[Question]: The S27X connected to the analog, and the value cannot be read on the cloud platform.
[Question]: The S27X connected to the analog, and the value cannot be read on the cloud platform.
【Solution】:
(2) Check the analog wiring. If you want to use the power supply output of S473, the wiring method is: DC Out'+' of the positive pole of the sensor, and AIN '+' of the negative pole of the sensor.
Another thing please confirm Whether the DIP switch is in the correct position (mA terminal or V terminal);
(3) The range of the sensor should be set correctly on the configuration software;
(4) Check if the device ID of S473 is the same as the slave address setting on the cloud platform; check whether the register address on the cloud platform is correct.