DAM series (analog type) as a Modbus slave device,can the analog alarm be realized on the S37x?

[Question]: DAM series (analog type) as a Modbus slave connected to the S37x series, can the analog alarm be realized on the S37x?

 [Answer]: Yes. On the S37x configuration software, open the slave mapping table, right-click "Edit Slave", and set the analog high and low limits. (Note: S17x,27x,37x,47x series products are supported, except for S270/271/272 and S372)